TITLE: HEATING,
VENTILATION, AND AIR CONDITIONING (HVAC)
DEFICIENCY 1: The
inspection date is on or between October 1 and March 31 and the permanently
installed heating source is not working or the permanently installed heating
source is working and the interior temperature is below 64 degrees Fahrenheit.
DEFICIENCY
2: The inspection date is on or between
October 1 and March 31 and the permanently installed heating source is working
and the interior temperature is 64 to 67.9 degrees Fahrenheit.
DEFICIENCY 3: Air conditioning system or device is not operational.
DEFICIENCY 4: Unvented space heaters that burns gas, oil, or kerosene
is present.
DEFICIENCY
5: Combustion chamber cover or gas shutoff valve is
missing from a fuel burning heating appliance.
DEFICIENCY
6: Heating system or device safety shield is
damaged or missing.
DEFICIENCY 7: The inspection date is on or between April 1 and
September 30 and a permanently installed heating source is damaged, inoperable,
missing, or not installed.
DEFICIENCY 8: Fuel burning heating system or device exhaust vent is
misaligned, blocked, disconnected, improperly connected, damaged, or missing.
DEFICIENCY 9- outsidde: The inspection date is on or between October 1 and March
31 and the permanently installed heating source is inoperable.
DEFICIENCY 1: The
inspection date is on or between October 1 and March 31 and the permanently
installed heating source is not working or the permanently installed heating
source is working and the interior temperature is below 64 degrees Fahrenheit.
DEFICIENCY
CRITERIA: The inspection date is on or between October 1 and
March 31.
AND the permanently installed heating source
is not working.
OR
The permanently installed
heating source is working and the interior temperature is below 64 degrees Fahrenheit.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 24
hours
DEFICIENCY 2:
The inspection date is on or between
October 1 and March 31 and the permanently installed heating source is working
and the interior temperature is 64 to 67.9 degrees
Fahrenheit.
DEFICIENCY CRITERIA: The
inspection date is on or between October 1 and March 31.
AND
The permanently installed
heating source is working and the interior temperature is 64 to 67.9 degrees Fahrenheit
HEALTH AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 3: Air conditioning system or device is not operational.
DEFICIENCY
CRITERIA: System or device does not turn on.
OR
System or device only produces hot or room
temperature air.
HEALTH AND SAFETY DETERMINATION: Moderate
CORRECTION TIMEFRAME: 30 days
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 4: Unvented space heater that burns gas, oil, or kerosene is
present.
DEFICIENCY
CRITERIA: Unvented space heater that burns gas, oil, or
kerosene is present.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 24
hours
DEFICIENCY 5: Combustion chamber cover or gas shutoff valve is missing
from a fuel burning heating appliance.
DEFICIENCY
CRITERIA: Combustion chamber cover or gas shutoff valve is
missing (i.e., evidence of prior installation, but is now not present or is
incomplete) from a fuel burning heating appliance.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 24
hours
DEFICIENCY 6: Heating system or device safety shield is damaged or
missing.
DEFICIENCY
CRITERIA: Heating system or device safety shield is damaged
(i.e., visibly defective; impacts functionality) or missing (i.e., evidence of
prior installation, but is now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 7: The inspection date is on or between April 1 and
September 30 and a permanently installed heating source is damaged, inoperable,
missing, or not installed.
DEFICIENCY
CRITERIA: The inspection date is on or between April 1 and
September 30.
AND
A permanently installed heating source is
damaged (i.e., visibly defective; impacts functionality).
OR
A permanently installed heating source is
inoperable (i.e., not meeting function or purpose, with or without visible
damage).
OR
A permanently installed heating
source is missing (i.e., evidence of prior installation, but is now not present
or is incomplete).
OR
A permanently installed heating
source is not installed.
HEALTH AND SAFETY DETERMINATION: Moderate
CORRECTION TIMEFRAME: 30 days
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 8: Fuel burning heating system or device exhaust vent is
misaligned, blocked, disconnected, improperly connected, damaged, or missing.
DEFICIENCY
CRITERIA: Fuel burning heating system or device is present.
AND
Exhaust vent is misaligned, blocked,
disconnected,
or improperly connected through to the ceiling
or wall.
OR
Exhaust vent is damaged (i.e.,
visibly defective; impacts functionality).
OR
Exhaust vent is missing (i.e., evidence of
prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME: 24
hours
HCV Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 24
hours
DEFICIENCY 9: The inspection date is on or between October 1 and March
31 and the permanently installed heating source is inoperable.
MORE INFORMATION: Heating, Ventilation, and Air
Conditioning (HVAC) Standard