TITLE: FIRE EXTINGUISHER
DEFICIENCY 1: FIRE EXTINGUISHER PRESSURE GAUGE READS OVER OR UNDER CHARGED
DEFICIENCY CRITERIA: Pressure gauge indicates that the fire extinguisher is over or under charged.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:                  24 hours
HCV Pass / Fail                                          Fail
HCV – CORRECTION TIMEFRAME:         24 hours
DEFICIENCY2: FIRE EXTINGUISHER SERVICE TAG IS MISSING, ILLEGIBLE OR EXPIRED
DEFICIENCY CRITERIA: The date on the service tag of any fire extinguisher has exceeded one year.
OR
The fire extinguisher tag is missing or illegible.
OR
A non-chargeable or disposable fire extinguisher is more than 12 years old (based on manufacture date).
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:                  24 hours
HCV Pass / Fail                                          Fail
HCV – CORRECTION TIMEFRAME:         24 hours
DEFICIENCY 3: FIRE EXTINGUISHER IS DAMAGED OR MISSING
DEFICIENCY CRITERIA: Fire extinguisher is damaged (i.e., visibly defective; impacts functionality).
OR
Fire extinguisher is missing (i.e., evidence of prior installation, but now not present or is incomplete)
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:                  24 hours
HCV Pass / Fail                                          Fail
HCV – CORRECTION TIMEFRAME:         24 hours
MORE INFORMATION: Fire Extinguisher Standard