TITLE: DOOR – Fire Labeled
DEFICIENCY 1: FIRE
LABELED DOOR DOES NOT OPEN.
DEFICIENCY 2: FIRE
LABELED DOOR DOES NOT CLOSE AND LATCH OR THE SELF-CLOSING HARDWARE IS DAMAGED
OR MISSING SUCH THAT THE DOOR DOES NOT SELF-CLOSE AND LATCH
DEFICIENCY 3: A FIRE LABELED DOOR ASSEMBLY HAS A HOLE OF ANY SIZE OR IS
DAMAGED SUCH THAT ITS INTEGRITY MAY BE COMPROMISED
DEFICIENCY 4: FIRE
LABELED DOOR SEAL OR GASKET IS DAMAGED OR
MISSING
DEFICIENCY 5: AN OBJECT IS PRESENT
THAT MAY PREVENT THE FIRE LABELED DOOR FROM CLOSING AND LATCHING OR
SELF-CLOSING AND LATCHING
DEFICIENCY 6: FIRE LABELED DOOR THAT
SERVES AS AN ENTRY DOOR CANNOT BE SECURED
DEFICIENCY
7: FIRE LABELED DOOR is
missing
DEFICIENCY 1: FIRE
LABELED DOOR DOES NOT OPEN.
DEFICIENCY CRITERIA:
Fire labeled door does not open such that it may limit
access between spaces.
HEALTH AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME:
24 Hours
HCV Pass / Fail Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 2:
FIRE LABELED DOOR DOES NOT CLOSE AND
LATCH OR THE SELF-CLOSING HARDWARE IS DAMAGED OR MISSING SUCH THAT THE DOOR
DOES NOT SELF-CLOSE AND LATCH
DEFICIENCY CRITERIA:
Fire labeled door does not close (i.e., door seats in
frame) and latch. OR Fire labeled door self-closing hardware is damaged (i.e.,
visibly defective; impacts functionality) or missing (i.e., evidence of prior
installation, but is now not present or is incomplete) such that the door does
not self-close (i.e., door seats in frame) and latch.
HEALTH
AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24 hours
HCV
Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 3: A FIRE LABELED DOOR ASSEMBLY HAS
A HOLE OF ANY SIZE OR IS DAMAGED SUCH THAT ITS INTEGRITY MAY BE COMPROMISED.
DEFICIENCY CRITERIA: A fire
labeled door assembly has a hole of any size.
OR
A fire labeled door assembly is damaged (i.e.,
visibly defective; impacts functionality) such that its integrity may be
compromised
HEALTH
AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24 hours
HCV
Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY
4: FIRE LABELED DOOR SEAL OR GASKET IS DAMAGED OR
MISSING
DEFICIENCY CRITERIA:
fire labeled door
seal or gasket is damaged (i.e. visibly defective; impacts functionality).
OR
A fire labeled door
seal or gasket is missing (i.e. evidence of prior installation, but now not
present or is incomplete).
HEALTH
AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24 hours
HCV
Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY
5: AN OBJECT IS PRESENT THAT MAY PREVENT
THE FIRE LABELED DOOR FROM CLOSING AND LATCHING OR SELF-CLOSING AND LATCHING
DEFICIENCY
CRITERIA: An object is present that may prevent the fire
labeled door from closing (i.e., door seats in frame) and latching.
OR
An object is present that may prevent the fire
labeled door from self-closing (i.e., door seats in frame) and latching
HEALTH AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME:
24 hours
HCV Pass / Fail Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 6: FIRE LABELED DOOR CANNOT BE SECURED
DEFICIENCY CRITERIA: Fire labeled door cannot be secured (i.e., access controlled) by at
least 1 installed lock.
HEALTH
AND SAFETY DETERMINATION: Severe
CORRECTION TIMEFRAME: 24 hours
HCV
Pass / Fail
Fail
HCV – CORRECTION TIMEFRAME: 30 days
DEFICIENCY 7: FIRE
LABELED DOOR is missing
DEFICIENCY
CRITERIA: Fire labeled door is missing (i.e., evidence of
prior installation, but is now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:
24 hours
HCV Pass / Fail Fail
HCV – CORRECTION TIMEFRAME: 24 Hours
MORE INFORMATION:
Door – Fire Labeled Standard