TITLE: DOOR
– ENTRY
DEFICIENCY 1: ENTRY DOOR WILL NOT OPEN
DEFICIENCY 2: ENTRY DOOR WILL NOT CLOSE
DEFICIENCY 3: ENTRY DOOR SELF-CLOSING MECHANISM IS DAMAGED,
INOPERABLE, OR MISSING
DEFICIENCY 4:ENTRY DOOR CANNOT BE
SECURED.
DEFICIENCY 5: HOLE, SPLIT, OR CRACK THAT PENETRATES COMPLETELY
THROUGH ENTRY DOOR
DEFICIENCY 6: ENTRY DOOR IS MISSING
DEFICIENCY 7: ENTRY DOOR SURFACE IS DELAMINATED OR SEPARATED
DEFICIENCY 8: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS DAMAGED OR
MISSING
DEFICIENCY 9: ENTRY
DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY 10: Entry
door component is damaged, inoperable, or missing and it does not limit the
door’s ability to provide privacy or protection from weather or infestation.
DEFICIENCY 1: ENTRY DOOR WILL NOT OPEN
DEFICIENCY
CRITERIA: Entry door does not open.
HEALTH AND SAFETY DETERMINATION:
Moderate
CORRECTION TIMEFRAME: 30 days
HCV
Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30 days
DEFICIENCY 2: ENTRY
DOOR WILL NOT CLOSE
DEFICIENCY
CRITERIA: Entry door does not close (i.e., door
seats in frame).
HEALTH
AND SAFETY DETERMINATION:
Severe
CORRECTION TIMEFRAME: 24 hours
HCV
Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30 days
DEFICIENCY
3: ENTRY DOOR SELF-CLOSING MECHANISM IS
DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY
CRITERIA: The self-closing mechanism is damaged
(i.e., visibly defective; impacts functionality).
OR
The self-closing mechanism does not pull
the door closed and engage the latch.
OR
The self-closing mechanism is missing (i.e.,
evidence of prior installation, but now not present or is incomplete).
HEALTH AND SAFETY DETERMINATION:
Moderate
CORRECTION TIMEFRAME: 30
days
HCV Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30
days
DEFICIENCY 4:ENTRY DOOR CANNOT BE SECURED.
DEFICIENCY CRITERIA:
Entry door cannot be secured (i.e. access controlled) by at least 1
installed lock.
HEALTH AND SAFETY DETERMINATION:
Severe
CORRECTION TIMEFRAME: 24 hours
HCV Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30
days
DEFICIENCY 5: HOLE,
SPLIT, OR CRACK THAT PENETRATES COMPLETELY THROUGH ENTRY DOOR
DEFICIENCY CRITERIA:
A hole 1/4" or greater in diameter that penetrates all the way through the
door.
OR
A split or crack 1/4" or greater in
width that penetrates all the way through the door.
OR
A hole or a crack with separation is
present, or the glass is missing within the door, side lites, or transom.
HEALTH
AND SAFETY DETERMINATION:
Moderate
CORRECTION
TIMEFRAME: 30 days
HCV
Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30 days
DEFICIENCY
6: ENTRY DOOR IS MISSING
DEFICIENCY CRITERIA:
The entry door is missing.
HEALTH AND SAFETY DETERMINATION:
Severe
CORRECTION TIMEFRAME: 24 hours
HCV Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30
days
DEFICIENCY
7: ENTRY DOOR SURFACE IS DELAMINATED OR
SEPARATED
DEFICIENCY CRITERIA:
There is delamination or separation of the door surface 2 inches wide or
greater.
OR
There is delamination or separation that
affects the integrity of the door (i.e., surface protection or the strength of
the door).
HEALTH AND SAFETY DETERMINATION:
Moderate
CORRECTION TIMEFRAME: 30
days
HCV Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30
days
DEFICIENCY
8: ENTRY DOOR FRAME, THRESHOLD, OR TRIM IS
DAMAGED OR MISSING
DEFICIENCY CRITERIA:
The entry door frame, threshold, or trim is damaged (i.e. visibly defective;
impacts functionality).
OR
The entry door frame, threshold, or trim
is missing (i.e. evidence of prior installation, but now not present or is
incomplete).
HEALTH AND SAFETY DETERMINATION:
Moderate
CORRECTION TIMEFRAME: 30
days
HCV Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30
days
DEFICIENCY 9: ENTRY
DOOR SEAL, GASKET, OR STRIPPING IS DAMAGED, INOPERABLE, OR MISSING
DEFICIENCY CRITERIA:
The entry door seal, gasket, or stripping is:
- damaged (i.e. visibly defective;
impacts functionality);
- inoperable (i.e. overall system or
component thereof not meeting function / purpose; with or without visible
damage); or
- missing (i.e. evidence of prior
installation, but now not present or is incomplete).
AND ONE OF THE FOLLOWING CONDITIONS:
Condition 1:
- General door type: Results in a gap of
¼ inch wide or greater between the door slab and the stop molding on the jamb,
or the jamb itself, or between the bottom of the door and the threshold or
floor AND permits light around the closed door.
- Special door type: Results in a gap of
¼ inch wide or greater around or under the door or where the doors meet AND
permits light around the closed door or where the doors meet.
Condition 2:
- General door type: There is evidence of
water penetrating (e.g. water damage or dry rot) around or under the door.
- Special door type: There is evidence of
water penetrating (e.g. water damage or dry rot) around or under the door or
where the doors meet.
HEALTH
AND SAFETY DETERMINATION:
Moderate
CORRECTION
TIMEFRAME: 30 days
HCV
Pass / Fail Fail
HCV CORRECTION TIMEFRAME: 30 days
DEFICIENCY 10: Entry
door component is damaged, inoperable, or missing and it does not limit the
door’s ability to provide privacy or protection from weather or infestation.
DEFICIENCY CRITERIA:
Entry door component is damaged (i.e., visibly
defective; impacts functionality) and it does not limit the door’s ability to
provide privacy or protection from weather or infestation.
OR
Entry door component is
inoperable (i.e., component is not meeting function or purpose, with or without
visible damage), and it does not limit the door’s ability to provide privacy or
protection from weather or infestation.
OR
Entry door component is missing (i.e.,
evidence of prior installation, but it is now not present or is incomplete) and
it does not limit the door’s ability to provide privacy or protection from
weather or infestation.
HEALTH AND SAFETY DETERMINATION:
Low
CORRECTION TIMEFRAME: 60 days
HCV Pass / Fail Pass
HCV CORRECTION TIMEFRAME: N/A
MORE INFORMATION: Door
– Entry Standard