CALL FOR AID SYSTEM - NSPIREASSIST

Share
Go to content
CALL-FOR-AID SYSTEM
PURPOSE: Provides the resident with a means to alert emergency service.
DEFICIENCY 1: SYSTEM IS BLOCKED or pull cord is higher than 6 inches off the floor.
DEFICIENCY CRITERIA: Call-for-aid system is blocked.
OR
The pull cord end is higher than 6 inches off the floor.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:                       24hours
HCV PASS / FAIL                                            Fail
HCV – CORRECTION TIMEFRAME:           30 days
DEFICIENCY 2: SYSTEM DOES NOT FUNCTION PROPERLY
DEFICIENCY CRITERIA: A call-for-aid system does not emit sound or light or send signal to annunciator.
OR
The annunciator does not indicate the correct corresponding room.
OR
Pull cord is missing.
OR
Pull cord is tied up such that it cannot be engaged.
HEALTH AND SAFETY DETERMINATION: Life-Threatening
CORRECTION TIMEFRAME:                       24 hours
HCV PASS / FAIL                                             Fail
HCV – CORRECTION TIMEFRAME:             24 hours
MORE INFORMATION: Call-for-Aid System Standard
Back to content